EDI LCL2400 CLASS L 600V TIME-DELAY
Part #
LCL2400
Availability
Item will ship in 3 to 7 business days
Item will ship in 3 to 7 business days
Average Rating
0.0/5 from 0 reviews
Class
L
Amps
2400A
Voltage
600V
Type
Time Delay
Compare
Please log in to order products.
Product Information
Catalog Symbol: LCL
Time-Delay - 5 seconds (minimum) at 500% rated current
Current-Limiting
Volts: 600Vac (or less)
IR: 200kA RMS Sym.
Mounting: Bolt Mount
Features
o LCL general purpose copper link fuses.
o Copper links result in a minimum 5 second time-delay at 500% Amp rating.
o Current-limiting- provides component short-circuit protection.
o 200kAIR complies with NEC Sections 110-9 in today™s large capacity systems.
o Selective coordination (blackout prevention) when sized per published coordination ratios.
o No fuse reducers required
Related Files
Manufacturer
UPC
782634605249